OSHA REQUIREMENTS
BASE PLATE :
- BASEPLATE NEED TO HAVE MINIMUM 4 ANCHOR BOLTSA
- USAGE OF LEVELING NUT OR LEVELING PLATE SHOULD BE DISCUSSED WITH ERECTOR
- DETAILER SHOULD REFER TO DESIGN DRAWINGS TO PROVIDE OVERSIZED HOLES IN BASE PLATE ,IF INFORMATION MISSING THEN WE NEED TO REFER TABLE C-J9.1 AND 14.2 OF AISC BOOK.
COLUMN
- COLUMN SPLICE SHOULD BE AT 4'-0 FROM FINISHED FLOOR
- ALL PERIMETER COLUMNS SHOULD HAVE SAFETY HOLES FOR WIRE GUARD RAIL ONE AT 1'-9 FROM FINISHED FLOOR AND SECOND AT 3'-6 FROM FINISHED FLOOR
- ALL COLUMNS SHOULD BE PROVIDED WITH LIFTING HOLE SPECIALLY TIER COLUMNS,NORMALLY LIFTING HOLE DIA IS 2'-0.
- ALL COLUMNS SHOULD HAVE CORRECT ORIENTATION MARK TO ERECT THE COLUMN.
- EXTENDED SHEAR TAB CONNECTION TO BE FOLLOWED WHERE BOLT ACCESS IS BLOCKED BY FLANGES.
BEAM:
- MINIMUM OF TWO BOLTS REQUIRED AT EACH END OF BEAM FOR ERECTIO
- D/2 RULE TO BE SATISFIED AT EACH CONNECTION TO SATISFY REQUIRED LOADS
- ALL DOUBLE ANGLE CONNECTIONS AT COLUMN WEB OR BEAM WEBMUST HAVE STAGGERED CLIP ANGLES OR A BEAM SEAT OR A TOP FLANGE CLIP ANGLE .WHEN NOT POSSIBLE TO PROVIDE SAFETY CONNECTIONS THE DETAILER SHOULD ADD A NOTE OF WARNING TO THE ERECTOR ON EPLANS.
JOISTS:
- IF JOIST SPAN MORE THAN 40'-0 THEN WE SHOULD BE PROVIDED WITH 2 ERECTION BOLTS
- VERTICAL STABILZER PLATE NEED TO BE PROVIDED, THIS PLATE SHOULD BE OF MINIMUM 6"X6" AND 3" BELOW THE BOTTOM OF JOIST, WITH 13/16DIA HOLE FOR GUYING OR PLUMBING CABLES.
DECK :
- DECK SUPPORT MAY BE REQUIRED AT DECK CUTOUTS NEAR BEAM TO BEAM OR BEAM TO COLUMN CONNECTIONS,REFER DESIGN DRAWING OR THE CLENT FOR PREFERRED METHOD
SNAGGING HAZARDS:
- AVOID SHARP CORNERS.
CONNECTIONS:
- USE BEARING CONNECTIONS AND AVOID HANGING CONNECTIONS.
TRIPPING HAZARDS:
- ANY CONNECTIONS OR OBSTRUCTIONS SHOULD BE AVOIDED ON TOP OF BEAM OR JOIST.
FALL PROTECTION:
- MULTISTORAGE STRUCTURE REQUIRES GUARD RAIL CABLES AT FLOOR PERIMETER ,INTERIOR OPENINGS AND ROOF OPENINGS.THIS PROTECTION SUPPORT SHOULD BE AGREED UPON PRIOR TO COMENCEMENT OF DETAILING.
ERECTION AID:
- FOR FIELD WELDS OF TUBES OR BRACINGS ,WE NEED TO PROVIDE ERECTION BOLT OR ERECTION ANGLE FOR SUPPORT